CB-A2DIO8X8 Control Board

Figure 1: General view of the CB-A2DIO8X8 board

  • download
  • Manual v1.1

    CB-A2DIO8X8
    Controller Board

    01. Description

    The CB-A2DIO8X8 control board is designed to monitor up to 8 digital inputs and control 8 relay outputs. It is a programmable device suitable for industrial automation, designed for DIN rail mounting (9 DIN) and fits GAINTA D9MG cases.

    The board features 2 analog inputs (12-bit ADC), NTC-10K temperature sensing, and dual RS485 ports for Modbus RTU communication.

    02. Technical Specifications

    ParameterDetail
    Supply Voltage12V...24V DC
    Relay Outputs8 (NO contacts), 5.0A @ 250VAC
    Digital Inputs8 (Opto-isolated, 1.0MHz)
    Analog Input 10-10V or 4-20mA (Jumper J15)
    Analog Input 2NTC-10K Remote thermistor
    Communication2x RS485 (Modbus RTU)
    Operating Temp-20°C to +70°C
    Dimensions156.2 mm x 86.9 mm

    03. Wiring & Connections

    Power Supply

    The board requires a 12-24V DC power supply. Connection points are clearly marked on the power connector (Figure 2 in manual).

    Relay Outputs

    Contains 4 pairs of NO relay outputs (8 independent relays). Connection groups: COM12 (Relays 1-2), COM34 (3-4), COM56 (5-6), and COM78 (7-8). Each contact supports up to 5A.

    Digital Inputs

    8 high-speed optically isolated inputs (1.0MHz). These can process both "receive" and "source" signals per pair.

    Analog Input Configuration

    Jumper J15: When closed, CH1 operates in 4-20mA mode. When open, it operates in 0-10V mode. CH2 is dedicated to NTC-10K sensors.

    RS485 & Termination

    Two RS485 ports for Master/Slave daisy-chaining. If the device is at the end of the bus line, short terminal T to terminal B to activate the 120 Ohm terminator.